0,6 / 1 kV 3 × 185 + 1 × 95 CABLOS DE ALIMENTAÇÃO LV
Informação básica
Modelo: YJY
Descrição do produto
1. NORMAS APPLICALBE
O cabo deve ser projetado, fabricado e testado de acordo com as normas internacionais da seguinte forma:
Quality Control Standard |
|
ISO 9001 |
Quality Management Systems |
ISO 14001 |
Environmental Management Systems |
Component Material Standard |
|
IEC 60228 |
Conductors of insulated cables |
Cable Standard |
|
IEC 60502-1 |
Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) – Part 1:Cables for rated voltages of 1kV(Um=1.2kV) and 3kV(Um=3.6kV) |
IEC 60332-3-24 |
Test for vertical flame spread of vertically-mounted bunched wires or cables – Category C |
2. ESTRUTURA DE CABOS PARA CABLE DE 0,6 / 1KV
1)
CU / PVC / PVC / STA / FR-PVC 0,6 / 1 kV 3 × 185 + 1 × 95
Basic Structure |
Nominal Thickness mm |
Nominal Outer Diameter mm |
1.Copper conductor |
/ |
15.3 |
2.XLPE insulation |
1.6 |
18.5 |
3. Filler |
/ |
42.4 |
4. Wrapping tape |
0.2 |
43.0 |
5. PVC Inner sheath |
1.4 |
45.8 |
6. Galvanized steel tape armor |
0.5 |
47.8 |
7. FR-PVC Outer sheath |
2.6 |
53.0 |
3. REQUISITOS DE TESTE PARA CABOS DE ALIMENTAÇÃO LV
O teste do cabo deve ser conduzido de acordo com o padrão aplicável de cabos de alimentação de 0,6 / 1kV. Os seguintes itens de teste devem ser realizados de acordo com as normas IEC relevantes.
No. |
Test item |
Routine tests |
|
1 |
measurement of the electrical resistance of conductors |
2 |
Voltage test |
Sample tests |
|
1 |
conductor examination |
2 |
check of dimensions |
3 |
Hot set test for XLPE insulation |
4. INFORMAÇÕES DE EMBALAGEM PARA CABOS DE ALIMENTAÇÃO DE 0,6 / 1KV
Os cabos devem ser enrolados em tambores de aço e madeira. A marcação indelével deve ser impressa na superfície da flange do tambor de acordo com os requisitos do cliente.
Fábrica e EquipamentosPacote
Localização
Nossa honra
Grupo de Produto : Cabo de alimentação de baixa tensão